Current research projects

Image Investigation of coolants
Image Industry 4.0 membrane heat and mass exchanger (i-MWÜ4.0)
Image Panel with indirect evaporative cooling via membrane
Image Filter Tests
Image State of system and failure analyses
Image Low Temperature Tribology
Image Software modules
Image Electrical components in refrigeration circuits
Image Certification of efficient air conditioning and ventilation systems through the new "indoor air quality seal" for non-residential buildings
Image Investigation of materials
Image Non- invasive flow measurements
Image Cold meter
Image Laseroptical measurement
Image Reducing the filling quantity
Image Influenced melting point of water by magnetic field
Image Refrigerants, lubricants and mixtures

You are here:   /  Home


Corrosion inhibitor for ammonia absorption systems

EURONORM GmbH

07/2021-08/2023

Dr. rer. nat. Franziska Krahl

+49-351-4081-5421

An alternative to chromium(VI) compounds

Project management: Dr. Franziska Krahl, Dr. Steffen Feja

Unlike electrically driven compression chillers or compression heat pumps, ammonia absorption systems (chillers and heat pumps) are driven by thermal energy. If the thermal energy comes from solar thermal energy, geothermal energy or waste heat, for example, these machines can be operated without fossil fuels. The working substances water and ammonia used are naturally occurring compounds, do not contribute to global warming (GWP = 0) and also have no ozone depletion potential (ODP).

The research project focused on identifying a suitable corrosion inhibitor for ammonia absorption systems to replace chromium(VI) compounds. A strategy was developed to enable the investigation of a large number of potential alternatives. From a total of more than 200 substance combinations (test approaches), 12 promising alternatives for further laboratory tests were identified using a rapid test developed in the project.

The rapid test developed proved to be very efficient in terms of identifying potential corrosion inhibitors. By using sealed reaction chambers, this test can also be carried out at significantly higher temperatures, which means that conditions close to the application are already present during screening.

At the end of the research project, 3 chromium(VI)-free corrosion inhibitors for ammonia absorption systems will be available, the basic suitability of which has been proven in laboratory tests. Their effectiveness is now to be tested in demonstrators.


Your Request

Further Projects

Image

Heat2Power

Refining of fuel cell waste heat

Image

Reducing the filling quantity

How much refrigerant must be filled?

Image

Performance tests of condensing units

Does your condensing unit perform well?

Image

State of system and failure analyses

Cause of the failure unknown?