Current research projects

Image Innovative Manufacturing Technologies for Cryosorption Systems
Image Innovative cryogenic cooling system for the recondensation / liquefaction of technical gases up to 77 K
Image Performance tests of refrigerant compressors
Image Optimizing HVAC operation with machine learning
Image Low temperature – test facilities
Image In-situ investigation concerning the swelling behaviour of polymer materials under elevated pressures and temperatures
Image Energy efficiency consulting - cogeneration systems
Image Hybrid- Fluid for CO2-Sublimation Cycle
Image Hydrogen and methane testing field at the ILK
Image Low noise and non metallic liquid-helium cryostat
Image Overall System Optimization of Refrigeration Plant Systems for Energy Transition and Climate Protection
Image Tensile and compression testing
Image State of system and failure analyses
Image Software for test rigs
Image Development of test methods and test rigs for stationary integrated refrigeration units
Image Reduction of primary noise sources of fans

You are here:   /  Home


Testing of mobile leak detectors according to DIN EN 14624

auf Anfrage

Dipl.-Ing. (FH) René Seidel

+49-351-4081-5428

Performance test according to standard

Determination of the performance of mobile leak detectors

According to Regulation (EU) No. 517/2014, systems containing fluorinated greenhouse gases must be tested for leaks at regular intervals (varying between 6 months and 2 years) depending on the CO2 equivalent. In practice, mobile leak detectors are mainly used for this purpose.

To ensure the proper functioning of the equipment, Regulation (EC) 1516/2007 requires that refrigeration and air conditioning equipment and heat pumps with a charge > 3 kg of fluorinated greenhouse gases be tested for proper operation every 12 months. "The sensitivity of portable gas detection devices must be at least 5 g per year".

According to DIN EN 378-2 section 6.3.3.2, the detector must be calibrated at regular intervals according to the manufacturer's instructions.

The test procedure for at least annual inspections of the performance of mobile leak detectors and room monitors for halogenated refrigerants is described in DIN EN 14624.

For this check, use, for example, a testing device with a sliding or swiveling leak detector probe. The performance test includes:

  • static detection with detection limit
  • Response time
  • Cross sensitivity
  • dynamic detection limit
  • Detection limit with contaminated environment
  • Recovery time

For these tests, a test stand is available at the ILK Dresden on which mobile leak detectors can be tested for their performance.

To determine the performance, adjustable calibrated test leaks are filled with the appropriate test gases (e.g. R134a, R1234yf) and placed in the test stand. We would be pleased to perform this test for you. The test performed is certified with a test report. 

Please direct inquiries about testing mobile leak detectors with the appropriate test gases to the contact above.