Current research projects

Image Range of services laboratory analyses
Image Heat2Power
Image Brine (water)-water heat pump
Image Certifiable connection types in cryogenics
Image In-situ investigation concerning the swelling behaviour of polymer materials under elevated pressures and temperatures
Image High temperature heat pump
Image Low Temperature Measuring Service
Image Software for technical building equipment
Image Innovative small helium liquefier
Image Development of test methods and test rigs for stationary integrated refrigeration units
Image High Capacity Pulse Tube Cooler
Image Innovative Manufacturing Technologies for Cryosorption Systems
Image Service offer for Leak Detection and Tightness Test
Image Low Temperature Tribology
Image Test rigs for refrigeration and heat pump technology
Image Thermostatic Expansion Valves

You are here:   /  Home


Testing of mobile leak detectors according to DIN EN 14624

auf Anfrage

Dipl.-Ing. (FH) René Seidel

+49-351-4081-5428

Performance test according to standard

Determination of the performance of mobile leak detectors

According to Regulation (EU) No. 517/2014, systems containing fluorinated greenhouse gases must be tested for leaks at regular intervals (varying between 6 months and 2 years) depending on the CO2 equivalent. In practice, mobile leak detectors are mainly used for this purpose.

To ensure the proper functioning of the equipment, Regulation (EC) 1516/2007 requires that refrigeration and air conditioning equipment and heat pumps with a charge > 3 kg of fluorinated greenhouse gases be tested for proper operation every 12 months. "The sensitivity of portable gas detection devices must be at least 5 g per year".

According to DIN EN 378-2 section 6.3.3.2, the detector must be calibrated at regular intervals according to the manufacturer's instructions.

The test procedure for at least annual inspections of the performance of mobile leak detectors and room monitors for halogenated refrigerants is described in DIN EN 14624.

For this check, use, for example, a testing device with a sliding or swiveling leak detector probe. The performance test includes:

  • static detection with detection limit
  • Response time
  • Cross sensitivity
  • dynamic detection limit
  • Detection limit with contaminated environment
  • Recovery time

For these tests, a test stand is available at the ILK Dresden on which mobile leak detectors can be tested for their performance.

To determine the performance, adjustable calibrated test leaks are filled with the appropriate test gases (e.g. R134a, R1234yf) and placed in the test stand. We would be pleased to perform this test for you. The test performed is certified with a test report. 

Please direct inquiries about testing mobile leak detectors with the appropriate test gases to the contact above.


Your Request

Further Projects

Image

Software modules

Software for properties of refrigerants

Image

Verification of storage suitability of cryo tubes

Artificial aging of primary packaging for biobanking applications

Image

Preformance measurements of heat exchangers

Is the heat exchanger properly sized?

Image

Innovative small helium liquefier

Liquefaction rates from 10 to 15 l/h

Image

Filter Tests

INDUSTRIAL AND LABORATORY PRECIPITATORS