Current research projects

Image State of system and failure analyses
Image Combined building and system simulation
Image Optimizing HVAC operation with machine learning
Image Pulse-Tube-Refrigerator with sealed compressor
Image Investigation of coolants
Image All-in-one device for freeze-drying and production of biomaterial
Image Micro heat exchangers in refrigeration
Image Calibration of Low Temperature Sensors
Image In-Situ-Swelling Behaviour of Polymer Materials in Flammable Fluids
Image Overall System Optimization of Refrigeration Plant Systems for Energy Transition and Climate Protection
Image Low Temperature Measuring Service
Image Measurement of insulated packaging
Image Cryostats, Non-Metallic and Metallic
Image Low Temperature Tribology
Image Investigation according to DIN EN ISO 14903
Image Innovative Manufacturing Technologies for Cryosorption Systems

You are here:   /  Home


Investigation according to DIN EN ISO 14903

Dipl.-Ing. (FH) René Seidel

+49-351-4081-5428

These tests according to DIN EN ISO 14903 are possible at ILK Dresden

§7.4 Tightness Test

§7.6 Pressure- Temperature- Vibration Test

§7.7 Simulation Operating

§7.8 Freezing Test

§7.9 Pressure Test

§7.10 Vacuum Test

§7.11 Compatibility Test

§7.12 Fatigue Test

 

§7.4 Tightness Test

  • Tightness control according to classification in DIN EN ISO 14903 at room temperature
  • In each case per connection or component (test sample) before and after the respective modules
  • Permissible leakage rate (helium) depending on the selected tightness control level E.g. A1 with Q ≤ 7,5E-7 Pa m³/s = 7,5E-6 mbar l/s @ 10 bar rel., 20 °C

  • Testing with helium gas detector in vacuum method or substitute method

  • Procedure section 10 according to DIN EN 13185, Detection limit 5,0E-13 Pa m³/s helium

  • Test gas helium

§7.6 PTV Test and if necessary §7.7 Simulation Operating

  • Tmin: -40 °C (specified by the customer)
  • Tmax: +140 °C (specified by the customer)
  • Test pressure PSmax: 100 bar rel. (specified by the customer)
  • 50 Temperature changes
  • 200 Pressure pulses
  • Subsequent vibration test < 200 Hz, 1 Axis, 2 Mio vibrations, const. amplitude
  • Simulation Operating, E.g. 25x open and close the connection

§7.8 Freezing Test

  • Freezing test in a vacuum test chamber. The test specimen is exposed in a vacuum chamber filled with water at 500 mbar abs (+ 0, -100 mbar) for at least 10 min. The pressure is then increased to atmospheric pressure.

  • Afterward, the test specimens are stored at -15 °C (or below) for at least 30 min in a temperature-controlled cabinet and then exposed to water at ambient temperature for at least 5 min., these steps are repeated a total of 30 times

§7.9 Pressure Test

  • The pressure test is performed at 5xPS for 1 minute
  • Medium oil

§7.10 Vacuum Test

  • The test samples are subjected to the test to confirm that they are able to withstand a vacuum with an absolute pressure of 6.5 kPa for 1 h without leakage.
  • For this purpose, the pressure is monitored and it is checked whether the pressure increase Δp after 1 h is less than 0.2 kPa. The effect of the temperature change on the pressure is taken into account.

§7.11 Compatibility Test

  • Investigation into the chemical compatibility of the materials

  • Aging for 336 h at 50 °C in refrigerant-oil atmosphere (for elastomer materials)

  • Aging for 1000 h at 50 °C in refrigerant-oil atmosphere (for thermoplastic materials)

  • Determination of mass, volume and hardness before and after aging

§7.12 Fatigue Test

  • Fatigue test, 250.000 Pressure cycles at max. 50 changes per minute

  • Test range between test pressure PS and atmospheric pressure, test medium: water


Your Request

Further Projects

Image

Low Temperature Tribology

Tribological studies at cryogenic temperatures

Image

Investigation of coolants

Secondary loop refrigerants

Image

Refrigerants, lubricants and mixtures

Determination of working fluid properties

Image

Reduction of primary noise sources of fans

...using numerical and experimental methods with contra-rotating axial fan