Current research projects

Image Investigation according to DIN EN ISO 14903
Image Optimizing HVAC operation with machine learning
Image Certifiable connection types in cryogenics
Image In-situ investigation concerning the swelling behaviour of polymer materials under elevated pressures and temperatures
Image Low Temperature Measuring Service
Image Ionocaloric cooling
Image Development of a Cryogenic Magnetic Air Separation Unit
Image Software modules
Image In-Situ-Swelling Behaviour of Polymer Materials in Flammable Fluids
Image Preformance measurements of heat exchangers
Image Laseroptical measurement
Image Multifunctional electronic modules for cryogenic applications
Image Cool Up
Image Intelligent innovative power supply for superconducting coils
Image Ice Slurry Generation
Image High temperature heat pump

You are here:  Home /  Research and Development


Development of test methods and test rigs for stationary integrated refrigeration units

BMWi Euronorm Innokom

02/2017 – 07/2019

Andreas Peusch

+49-351-4081-5221

How efficient is my refrigeration unit?

The objective of the R&D project was the development of a test method for stationary integrated refrigeration units. The test method comprises different device variants, like ceiling mounted, wall mounted or split refrigeration units. The method provides reliable performance data and thus enables a manufacturer-independent efficiency comparison.

Measurements in the 3- or 4-chamber measurement setup were carried out using the calorimeter method with compensation of the ambient conditions. This enabled the measurements of devices with low cooling capacity (0.5 - 4 kW).

In the selected test setup (Figure 1), the cooling capacity is measured indirectly via an electrical power of the compensation heating. To determine the total cooling capacity, the heat input into the calorimeter room and, if necessary, internal loads (sensible and latent heat) have to be added together.

The test method comprises following features:

  • Suitable for low temperature devices (-20 °C) and normal temperature cooling (0 °C)
  • Measurement in the calorimeter room (3- or 4-zone concept)
  • Determination of heat input via enclosure surfaces before power measurement
  • Establishment of equilibrium conditions (settling phase) of the temperatures to be set (up to 24 h)
  • Measuring period up to 6 h with permissible tolerance band of 0.2 K

Conclusion:

  • Results were included in new test standard prEN 17432
  • Establishment of a uniform Europe-wide comparison criterion
  • Performance and efficiency data on a uniform basis leads to higher confidence and thus also to lower consumption costs

Your Request

Further Projects - Research and Development

Image

Filter Tests

INDUSTRIAL AND LABORATORY PRECIPITATORS

Image

Low Temperature Tribology

Tribological studies at cryogenic temperatures

Image

Refrigerants, lubricants and mixtures

Determination of working fluid properties

Image

Reduction of primary noise sources of fans

...using numerical and experimental methods with contra-rotating axial fan

Image

Micro fluidic expansion valve

for increasing of the efficiency of small and compact cooling units